LOOK AT HERE
 
Why CHEMetrics?
Catalogue PDF
Applications
Trade Shows
Kit Instructions
Frequently Asked Questions
 
 
  SEARCH
 
Enter text to Search:


 
 
Vietnamese
 
 
Jump to Method
  DEHA
 
Methods

Dissolved oxygen in boiler system water causes corrosion and pitting of metal surfaces, which can lead to boiler inefficiency, equipment failure, and system downtime. DEHA (N, N Diethylhydroxylamine) is added to boiler system water as an oxygen scavenger to keep the dissolved oxygen levels as low as possible.

The PDTS Method

Reference: J. A. Tetlow and A. L. Wilson, “Determination of Iron in Boiler Feedwater,” Analyst, 1958.

The test kits employ the PDTS chemistry, in which DEHA reduces iron III (ferric state) to iron II (ferrous state), which readily reacts with PDTS (3-(2-pyridyl)-5,6-bis(4-phenylsulfonic acid)-1,2,4-triazine disodium salt) to form a pink-purple colored complex in direct proportion to the DEHA concentration. Test results are expressed in ppb (mg/L) or ppm (mg/L) DEHA.

The Ceric Sulfate Titrimetric Method

Reference: Developed by CHEMetrics, Inc.

CHEMetrics developed a titrimetric method that employs a ceric sulfate titrant and ferroin end point indicator. DEHA reduces ferric iron to the ferrous state, and the resulting ferrous iron is titrated with the ceric sulfate titrant. Test results are expressed in ppm (mg/L) DEHA.
 
Click to View MSDS and Kit instructions
 
  Visual Kits
0-400 & 400-3000 ppb
15 ppb / Method: PDTS
  Cat#
CHEMets Kit K-3902

CHEMets Refill, 30 ampoulesR-3902

Activator Solution Pack, six 10 mL bottles, Shelf-life 2 yearsA-3900

Low Range Comparator, Shelf-life 2 years: 0, 30, 60, 100, 150, 200, 300, 400 ppbC-3901

High Range Comparator, Shelf-life 2 years: 400, 600, 800, 1000, 1200, 1600, 2000, 2500, 3000 ppbC-3902

Kit comes in a plastic case and contains everything needed to perform 30 tests: Refill, Low and High Range Comparator, Activator Solution, 25 mL sample cup, instructions and MSDS.
Click here to Buy Now Complete Kits!

25-250 ppm
25 ppm / Method: Ceric Sulfate Titrant with Ferroin Indicator
  Cat#
Titrets Kit K-3925

Increments: 25, 27.5, 30, 32.5, 35, 37.5, 40, 45, 50, 62.5, 75, 87.5, 100, 125, 175, 250 ppm

Kit comes in a cardboard box and contains everything needed to perform 30 tests: thirty ampoules, thirty valve assemblies, Activator Solution, titrettor, 25 mL sample cup, instructions, and MSDS.
Click here to Buy Now Complete Kits!

 
  Instrumental Kits
0.15-2.00 ppm
PDTS
  Cat#
Vacu-vials Kit K-3903

Kit comes in a cardboard box and contains everything needed to perform 30 tests: thirty ampoules, Activator Solution1, 25 mL sample cup, ampoule blank, instructions, calibration table, and MSDS.
Click here to Buy Now Complete Kits!

 
Kit Components common to DEHA
Description Cat#

Sample Cup Pack, 25 mL (6 ea)A-0013

Ampoule Blank Pack (5 ea)A-0023

Titrettor Pack (1 ea)A-0053
Click here to Buy Now Complete Kits!
 
Tel: 02 87065400
Email: sales@watertestsystems.com.au
Watertest Systems Pty Ltd 2006
Website designed by DeboSoft